ARTICLE VII. INTERNATIONAL FUEL GAS CODE
Sec. 8-700.
Adopted; where filed; amendments.
(a) That certain
document known as the "International Fuel Gas Code, 2006 Edition,"
which has been published as a code in book form by the International Code
Council, chapters two through seven and appendix chapters A, B and C, three (3)
copies with amendments of which are on file in the office of the city clerk,
and this same code and appendices are hereby referred to, adopted and made a
part hereof, as if fully set out in this article.
(b) The provisions
of this article, other than subsections (a) and (b) of this section, are
amendments to the International Fuel Gas Code as now or hereafter adopted in
subsection (a). All sections in this
article, other than subsections (a) and (b) of this section, shall be
considered to be both a part of this code and a part of the International Fuel
Gas Code.
(Ord. No. 2008.72,
12-11-08)
Charter reference—Adoption by reference, § 2.14.
State law reference—Adoption by
reference, A.R.S. § 9-801 et seq.
Sec.
303. Appliance location.
Section 303.3 is hereby amended as follows:
303.3. Prohibited locations. Appliances shall not be located in sleeping
rooms, bathrooms, toilet rooms, storage closets or surgical room, or in a space
that opens only into such rooms or spaces, or any room operating under negative
pressure unless the appliances are listed for that use except where the
installation complies with one of the following:
1. The appliance
is a direct-vent appliance installed in accordance with the conditions of the
listing and the manufacturer’s instructions.
2. Vented room
heaters, wall furnaces, vented decorative appliances, vented gas fireplaces,
vented gas fireplace heaters and decorative appliances for installation in
vented solid fuel-burning fireplaces are installed in rooms that meet the
required volume criteria of Section 304.5.
3. A single
wall-mounted unvented room heater is installed in a bathroom and such unvented
room heater is equipped as specified in Section 621.6 and has an input rating
not greater than six thousand (6,000) Btu/h (1.76 kW). The bathroom shall meet the required volume
criteria of Section 304.5.
4. A single
wall-mounted unvented room heater is installed in a bedroom and such unvented
room heater is equipped as specified in Section 621.6 and has an input rating
not greater than ten thousand (10,000) Btu/h (2.93 kW). The bedroom shall meet the required volume
criteria of Section 304.5.
5. The appliance
is installed in a room or space that opens only into a bedroom or bathroom, and
such room or space is used for no other purpose and is provided with a solid
weather-stripped door equipped with an approved self-closing device. All
combustion air shall be taken directly from the outdoors in accordance with
Section 304.6.
Section 303.7 is hereby amended as follows:
303.7. Pit locations. Appliances installed in pits or excavations
shall not come in contact with the surrounding soil. The sides of the pit or excavation shall be
held back a minimum of twelve (12) inches (305 mm) from the appliance. Where the depth exceeds twelve (12) inches
(305 mm) below adjoining grade, the walls of the pit or excavation shall be
lined with concrete or masonry. Such
concrete or masonry shall extend a minimum of four (4) inches (102 mm) above to
adjacent grade and shall have sufficient lateral load-bearing capacity to
resist collapse. The appliance shall be
protected from flooding in an approved manner.
Liquefied petroleum (LPG) appliances shall not be installed in a pit,
attic or other location that would cause a ponding or retention of gas.
(Ord. No. 2008.72,
12-11-08)
Sec. 304.
Combustion, ventilation and dilution air.
Section 304.1 is hereby amended as follows:
304.1. General.
Air for combustion, ventilation and dilution of flue
gases for appliances installed in buildings shall be provided by application of
one of the methods prescribed in Sections 304.5 through 304.9. Where the requirements of Section 304.5 are
not met, outdoor air shall be introduced in accordance with one of the methods
prescribed in Sections 304.6 through 304.9.
For LPG appliances, any duct serving the
lower opening
shall be at the floor level and slope to the outdoors without traps or
pockets. Direct-vent appliances, gas
appliances of other than Category I shall be provided with combustion
ventilation and dilution air in accordance with the equipment manufacturer’s
instructions.
(Ord. No. 2008.72,
12-11-08)
Sec. 305.
Installation.
Section 305.3, Elevation
of ignition source, Exception is hereby amended as follows:
EXCEPTIONS:
1. Elevation of the ignition source is not
required for appliances that are listed as flammable vapor resistant and for
installation without elevation.
2. Direct-vent appliances that obtain all combustion air directly
from the outdoors.
3. Clothes dryers installed in private
garages.
Section 305.7 is hereby amended as follows:
305.7. Clearances from grade. Equipment and appliances installed at grade
level shall be supported on a level concrete
slab or other approved material extending a minimum of three (3) inches
(76 mm) above finished grade or shall be suspended a minimum of six (6) inches
(152 mm) above finished grade.
(Ord. No. 2008.72,
12-11-08)
Sec. 404. Piping
system installation.
Section 404.9 is hereby amended as follows:
404.9.
Minimum burial depth. Underground piping systems shall be
installed a minimum depth of twelve (12) inches (305 mm) below grade for
metal, and eighteen (18) inches (457 mm) below grade for plastic piping.
(Ord. No. 2008.72,
12-11-08)
Sec. 406.
Inspection, testing and purging.
Section 406.4 is hereby amended as follows:
406.4. Test pressure measurement. Test pressure shall be measured with a
manometer or with a pressure-measuring device designed and calibrated to read,
record, or indicate a pressure loss caused by leakage during the pressure test
period. The source of pressure shall be isolated before the pressure tests are
made.
Section 406.4.1 is hereby amended as follows:
406.4.1. Test pressure. The test pressure to be used shall be no less
than ten (10) pounds per square inch (69 kPa) gauge pressure, or where approved
by the building official, the piping and valves may be tested at a pressure of
at least six (6) inches (152.4 mm) of mercury, measured with a manometer or
slope gauge. For welded piping, and for
piping carrying gas at pressures in excess of fourteen (14) inches (0.4 m)
water column pressure, the test pressure shall be no less than sixty (60)
pounds per square inch (413 kPa). Where
the test pressure exceeds one hundred twenty-five (125) psig (862 kPa gauge),
the test pressure shall not exceed a value that produces a hoop stress in the
piping greater than fifty percent (50%) of the specified minimum yield strength
of the pipe.
Section 406.4.2 is hereby amended as follows:
406.4.2. Test duration. Test duration shall be not less than fifteen
(15) minutes or for welded pipe and piping carrying gas at pressures in excess
of fourteen (14) inches (0.4 m) water column pressure, the test duration shall
be not less than thirty (30) minutes.
The duration of the test shall not be required to exceed twenty-four
(24) hours.
Section 406.4.3 is hereby added as follows:
406.4.3. Test Gauges. Tests required by this code which are
performed utilizing dial gauges shall be limited to gauges having the following
pressure increments or graduations:
406.4.3.1. Required pressure tests of ten (10) pounds
(69 kPa) or less shall be performed with gauges having increments of one-tenth
(1/10) pound (0.69 kPa) or less.
406.4.3.2. Required pressure tests exceeding ten (10)
pounds (69 kPa) but less than one hundred (100) pounds (690 kPa) shall be
performed with gauges having increments of one pound (7 kPa) or less.
406.4.3.3. Required pressure tests exceeding one hundred
(100) pounds (690 kPa) shall be performed with gauges having increments two (2)
psi (14 kPa) or less.
406.4.3.4. Pressure tests required by this code, which
are performed utilizing dial gauges, shall be limited to a gauge having a
maximum gauge rating not exceeding twice the applied test pressure.
(Ord. No. 2008.72,
12-11-08)
Secs. 8-701—8-799.
Reserved.