ARTICLE III. INTERNATIONAL RESIDENTIAL CODE
Sec. 8-300.
Adopted; where filed; amendments.
(a) That certain
document known as the "International Residential Code, 2006 Edition,"
which has been published as a code in book form by the International Code Council,
chapters two through forty-three, and appendix chapters A, B, C, G, H, J and K,
three (3) copies with amendments of which are on file in the office of the city
clerk, and this same code and appendices are hereby referred to, adopted and
made a part hereof, as if fully set out in this article.
(b) The provisions
of this article, other than subsections (a) and (b) of this section, are
amendments to the International Residential Code as now or hereafter adopted in
subsection (a). All sections in this
article, other than subsections (a) and (b) of this section, shall be
considered to be both a part of this code and a part of the International
Residential Code.
(Ord. No.
2008.72, 12-11-08)
Charter reference—Adoption by reference, § 2.14.
State law reference—Adoption by
reference, A.R.S. § 9-801 et seq.
Sec. R201.
General.
Section R201.4 is hereby amended as follows:
R201.4. Terms not defined. Where terms are not defined through the methods
authorized by this section, such terms shall have ordinarily accepted meanings
such as the context implies. Webster’s Third New International Dictionary of
the English Language, Unabridged, shall be considered as providing ordinarily
accepted meanings.
(Ord. No.
2008.72, 12-11-08)
Sec. R202.
Definitions.
Section R202 is hereby amended as follows:
EMERGENCY ESCAPE AND
RESCUE OPENING. An operable window, door or similar device
that provides for a means of escape that opens directly into a public street,
public alley, yard or court and provides access for rescue in the event of an
emergency.
EXTERIOR WALL. Any wall or element of a wall or any member
or group of members, which defines the exterior boundaries or courts of a
building and which has a slope of sixty (60) degrees or greater with the horizontal
plane.
(Ord. No.
2008.72, 12-11-08)
Sec. R301.
Design criteria.
Section R301.1.1 is hereby amended as follows:
R301.1.1. Alternative
provisions. As an alternative to
the requirements in Section R301.1 with prior approval of the building official
the following standards are permitted subject to the limitations of this code
and the limitations therein. Where
engineered design is used in conjunction with these standards the design shall
comply with the International Building
Code.
1.
2. American Iron
and Steel Institute (AISI), Standard
for Cold-Formed Steel Framing-Prescriptive Method for One- and Two-family
Dwellings (COFS/PM).
Table R301.2(1)
is hereby amended as follows:
TABLE R301.2 (1)
CLIMATIC AND GEOGRAPHICAL DESIGN CRITERIA
|
Ground snow load |
Wind speede (mph) |
Seismic design categoryg |
Subject to damage from |
Winter design tempf |
Ice shield Under-layment
requiredi |
Flood Hazardsh |
Air Freezing Indexj |
Mean Annual Temp.k |
|||
|
Weatheringa |
Frost line depthb |
Termitec |
Decayd |
||||||||
|
0 |
90 (3 second. gust) |
C |
Negligible |
12 inches |
moderate to heavy |
None to slight |
34 degrees |
N/A |
|
0 |
71.2°F |
Table 301.5 is hereby amended as follows:
TABLE R301.5
MINIMUM UNIFORMLY
DISTRIBUTED LIVE LOADS
(in pounds per square
foot)
|
USE |
LIVE LOAD |
|
Attics with limited storage b,
g, h |
20 |
|
Attics without storage b |
10 |
|
Decks e |
40 |
|
Exterior balconies |
60 |
|
Fire escapes |
40 |
|
Guardrails and handrails d |
200 i |
|
Guardrails in-fill components f |
50 i |
|
Passenger vehicle garages a |
50 a |
|
Rooms other than sleeping rooms |
40 |
|
Sleeping rooms |
40 |
|
Stairs |
40 c |
For SI: 1 pound per square foot = 0.0479 kPa, 1
square inch = 645 mm2, 1 pound = 4.45 N.
a. Elevated garage floors shall be capable of
supporting a 2,000-pound load applied over a 20-square-inch area.
b. Attics
without storage are those where the maximum clear height between joist and
rafter is less than 42 inches, or where there are not two or more adjacent
trusses with the same web configuration capable of containing a rectangle 42
inches high by 2 feet wide, or greater, located within the plane of the truss.
For attics without storage, this live load need not be assumed to act
concurrently with any other live load requirements.
c. Individual stair treads shall be designed
for the uniformly distributed live load or a 300-pound concentrated load acting
over an area of 4 square inches, whichever produces the greater stresses.
d. A
single concentrated load applied in any direction at any point along the top.
e. See
Section R502.2.1 for decks attached to exterior walls.
f. Guard
in-fill components (all those except the handrail), balusters and panel fillers
shall be designed to withstand a horizontally applied normal load of 50 pounds
on an area equal to 1 square foot. This load need not be assumed to act
concurrently with any other live load requirement.
g. For
attics with limited storage and constructed with trusses, this live load need
be applied only to those portions of the bottom chord where there are two or
more adjacent trusses with the same web configuration capable of containing a
rectangle 42 inches high or greater by 2 feet wide or greater, located within
the plane of the truss. The rectangle shall fit between the top of the bottom
chord and the bottom of any other truss member, provided that each of the
following criteria is met:
1. The
attic area is accessible by a pull-down stairway or framed opening in
accordance with Section R807.1; and
2. The
truss has a bottom chord pitch less than 2:12.
h. Attic
spaces served by a fixed stair shall be designed to support the minimum live
load specified for sleeping rooms.
i. Glazing
used in handrail assemblies and guards shall be designed with a safety factor
of 4. The safety factor shall be applied to each of the concentrated loads
applied to the top of the rail, and to the load on the in-fill components.
These loads shall be determined independent of one another, and loads are
assumed not to occur with any other live load.
(Ord. No.
2008.72, 12-11-08)
Sec. R309.
Garages and carports.
Section R309.1 is hereby amended as follows:
R309.1. Opening protection. Openings from a private garage directly into a room used
for sleeping purposes shall not be permitted. Other openings between the garage
and residence shall be equipped with solid wood doors not less than one and
three-eighths (1-3/8) inches (35 mm) in thickness, solid or honeycomb core
steel doors not less than one and three-eighths (1-3/8) inches (35 mm) thick,
or twenty (20) minute fire-rated doors.
Doors providing opening protection shall be maintained self-closing and
self-latching.
Section R309.2 is hereby amended as follows:
R309.2. Separation required. The garage shall be separated from the residence and its
attic area by not less than one-half (1/2) inch (12.7 mm) gypsum board applied
to the garage side. Garages beneath
habitable rooms shall be separated from all habitable rooms above by not less
than five-eighths (5/8) inch (15.9 mm) Type X gypsum board or equivalent. Where the separation is a floor-ceiling
assembly, the structure supporting the separation shall also be protected by
not less than one-half (1/2) inch (12.7 mm) gypsum board or equivalent.
EXCEPTION:
Buildings protected with an automatic fire sprinkler system, including
the private garage, the separation shall be permitted to be limited to a
minimum one-half (1/2) inch (12.7 mm) gypsum board applied to the garage side.
(Ord. No.
2008.72, 12-11-08)
Sec. R311. Means
of egress.
Section R311.4.4 is hereby amended as follows:
R311.4.4. Type of lock
or latch. All egress doors shall be
readily openable from the side from which egress is to be made without the use
of a key or special knowledge or effort.
EXCEPTION:
Group R, Division 3 Occupancies and individual dwelling units and guest
rooms within Group R, Division 1 Occupancies.
Such occupancies may be provided with a night latch, double keyed
deadbolt or security chain, provided such devices are openable from the inside
without the use of a tool.
(Ord. No.
2008.72, 12-11-08)
Sec. R313.
Smoke alarms and fire sprinklers.
Section R313.4 is hereby added as follows:
R313.4. Fire Sprinklers. All areas of new buildings or structures, and
other locations required by this chapter, shall be provided with an automatic
fire sprinkler system complying with IBC Section 903.3.1.1, 903.3.1.2 or
903.3.1.3 as applicable.
EXCEPTION:
Automatic fire sprinkler protection systems shall not be required for
the following:
1. R-3
Occupancies of five thousand (5,000) square feet or less and other buildings or
structures accessory to R-3 Occupancies.
Section R313.4.1 is hereby added as follows:
R313.4.1. Additions. Automatic fire sprinkler protection systems
are not required in existing non-sprinklered R-3 Occupancies or additions
thereto.
(Ord. No.
2008.72, 12-11-08)
Sec. R325.
Building security.
Section R325 is hereby added as follows:
R325.1. Scope.
The provisions of this chapter shall apply to openings into dwelling
units and to openings between attached garages and dwelling units. Door openings, including vehicular access
doors in enclosed attached garages shall be in accordance with the provisions
of this chapter.
EXCEPTIONS:
1. An
opening in an exterior wall when all portions of such openings are more than
twelve (12) feet (3658 mm) vertically or six (6) feet (1829 mm) horizontally
from an accessible surface of any adjoining yard, court, passageway, public
way, walk, breezeway, patio, planter, porch or similar area.
2. An
opening in an exterior wall when all portions of such openings are more than
twelve (12) feet (3658 mm) vertically or six (6) feet (1829 mm) horizontally
from the surface of any adjoining roof, balcony, landing, stair tread, platform
or similar structure or when any portion of such surface is itself more than
twelve (12) feet (3658 mm) above an accessible surface.
3. Any
opening in a roof when all portions of such roof are more than twelve (12) feet
(3658 mm) above an accessible surface.
4. Openings when the small dimension is six (6)
inches (152 mm) or less, provided that the closest edge of the opening is at
least thirty-six (36) inches (914 mm) from the locking device of the door or
window assembly.
5. Openings
protected by required fire door assemblies having a fire-endurance rating of
not less than forty-five (45) minutes.
R325.2. Swinging doors.
R325.2.1. General.
Swinging doors shall be one of the following:
1. Wood flush‑type
door one and three-fourths (1‑3/4) inches thick minimum.
2. Wood panel‑type
door one and three-fourths (1‑3/4) inches thick minimum with all panels
fabricated from material not less than three-eighths (3/8) inch in thickness;
provided all shaped portions of the panels are not less than one-fourth (1/4)
inch thick.
3. Ferrous metal
doors of solid or hollow core construction with surfaces not less than
twenty-four (24) gauge in thickness.
4. Other metal
doors with surfaces not less than the equivalent of sixteen (16) gauge sheet
metal (0.06 inch) in thickness.
R325.2.2. Locking hardware. Single swinging doors and the active leaf of
doors in pairs shall be equipped with an approved exterior key operating
deadbolt or locking device as follows:
1. Strike
deadbolts with a minimum throw of one inch and an embedment of not less than
five-eighths (5/8) inch into the holding device receiving the projected bolt.
2. Hook shape or
expanding lug deadbolts with a minimum throw of three-fourths (3/4) inch.
3. Deadbolts or
locks which automatically activate two (2) or more deadbolts with an embedment
of not less than one-half (l/2) inch into the holding device receiving the
projected bolts.
The inactive leaf of doors in pairs shall be equipped with
manually or automatically operated hardened bolts at the top and bottom, with
an embedment not less than one-half (1/2) inch into the device receiving the
projected bolt.
Cylinder guards shall be installed on all mortise or rim‑type
cylinder locks whenever the cylinder projects beyond the face of the door or is
otherwise accessible to gripping tools.
R325.3. Windows.
Window assemblies regulated by this chapter which are designed to be
openable shall be constructed and installed so as to prohibit raising, sliding,
or removal of the moving section while in the closed and locked position,
unless such windows are protected by approved metal bars, screens or
grilles. Louvered windows regulated by
this chapter shall be protected by approved metal bars or grilles.
R325.4. Upward acting doors. Upward acting doors shall be secured with a
cylinder lock, padlock with a hardened steel shackle and hardened steel hasp,
metal slide bar, bolt or equivalent device, unless secured by electric power
operation.
Cylinder guards shall be installed on all mortise or rim‑type
cylinder locks whenever the cylinder projects beyond the face of the door or is
otherwise accessible to gripping tools.
(Ord. No.
2008.72, 12-11-08)
Sec.
R401. General.
Section R401.1 is hereby amended by adding Exception 3 as
follows:
3. Where
a design is not provided, the minimum foundation requirements for stud and
concrete masonry bearing walls shall be as set forth in Table R403.1.
(Ord. No.
2008.72, 12-11-08)
Sec.
R403. Footings.
Table
R403.1 is hereby amended as follows:
TABLE R403.1
FOUNDATIONS FOR STUD AND CONCRETE MASONRY
BEARING WALLS – MINIMUM REQUIREMENTS
|
Number of Floors Supported by the Foundation3 |
Thickness
of Foundation Wall2 (inches
– Nominal Dimension) |
Width
of Footing2,4 (W)\ (inches) |
Thickness
of Footing (inches) |
Depth
Below Undisturbed Soil (inches) |
|||
|
Stud
Wall |
|||||||
|
Concrete |
Masonry5 |
Stud Wall1 |
Masonry Wall |
Stud Wall |
Masonry
Wall |
||
|
1 |
6 |
6 |
12 |
16 |
6 |
8 |
12 |
|
2 |
8 |
8 |
15 |
20 |
7 |
8 |
18 |
|
3 |
10 |
8 |
18 |
24 |
8 |
8 |
24 |
For
SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m2.
1. Interior stud bearing walls may be
supported by isolated footings. The footing width and length shall be twice the
width shown in this table and the footings shall be spaced not more than 6 feet
(1,829 mm) on center.
2. A
minimum of two (2) #4 reinforcing bars (minimum grade 40) are required in the
footing/stem concrete. If metal hold downs are used, one #4 horizontal
reinforcing bar must be placed within the top 6 of the stem wall.
3. Foundations may support a roof in addition to the
stipulated number of floors. Foundations supporting roofs only shall be as
required for supporting only one floor.
4. Isolated
columns carrying loads in excess of 750 lbs shall be supported on minimum 4
square feet of footing, with minimum width of 24 inches. Maximum bearing
pressure from service loads shall not exceed 1500 psf unless recommended by the
soils report.
5. Foundation
wall width may not be less than the width of the masonry wall.
(Ord. No.
2008.72, 12-11-08)
Sec. R614. Earthen
wall structures.
Section R614 is hereby added as follows:
R614.1. General. Earthen structures with any site condition may be
designed with accepted engineering practice for earthen wall structures and
with provisions of this section.
R614.1.1. Earthen materials. This section shall establish minimum standards for
safety for construction of earthen materials structures, collectively known as
adobe, burnt adobe, rammed earth, and hydraulic pressed unit construction.
R614.1.2. Professional
registration required. Plans and specifications designed under the
provisions of R614 shall be prepared by a registered professional architect or
engineer licensed in the state for which the project is to be constructed.
R614.2. Minimum thickness. This minimum thickness of earthen structures
shall be designed to limit tension to zero unless tensil reinforcement is
provided. Walls shall be designed to meet forces prescribed by IBC Chapter
16. The measurement of height of walls
shall be the distance between points of lateral support. Wall thickness shall be measured from face to
face of each wall withe. The thickness
of walls using racked joints shall be the surface to surface distance of the
mortar joints. The withes of wall
sections shall not be combined without cross bonding of the masonry units
throughout the structural element. Cross
bonding shall mean overlapping of not less than one-third (1/3) of the
dimension of the masonry units.
R614.3. Support conditions. Earthen structures shall be supported on a solid
concrete, solid masonry foundation system the width of which shall be not
greater than one-sixth (1/6) inch narrower than the earthen structure which it
supports. Earthen structures shall not be
less than six (6) inches above adjacent grade.
R614.4. Corbeled wall elements. The maximum corbelled projection
beyond the face of the wall shall not be more than four (4) inches. Such corbeled projections shall add
additional thickness to the wall, the opposite face of the wall remaining plane
with the primary wall plane.
R614.5. Moisture barrier. A moisture barrier equal to thirty (30) lb. asphalt
impregnated building paper, or equivalent moisture resistant barrier, shall be
installed between the supporting foundation and the earthen wall material.
R614.6. Allowable stresses. Allowable compressive, tensile and shear stresses in
earthen structures shall not exceed the values prescribed in Table
R614.6.A. In determining the stresses,
the effects of all loads and conditions of loading and the influences of all
forces affecting the design and strength of the several parts shall be
considered. Bolt values shall not exceed
those set forth in International Building Code Table 2109.8.3.1.
R614.6.1. Combined units. In walls composed of different kinds or grades of units,
materials or mortars, the maximum stress shall not exceed the allowable stress
for the weakest of the combination of units, materials and mortars of which the
wall is composed. The net thickness of
any facing unit of earthen materials used to resist stress shall not be less
than three (3) inches (76 mm).
When dissimilar materials, (e.g. concrete masonry or steel),
is used to support earth wall construction, such elements shall be structurally
isolated from other earth wall elements.
The design shall recognize, with specific detailing, the effects
shrinkage of the earth wall construction may have on the structural integrity
of the structure.
TABLE R614.6.A
ALLOWABLE STRESSES FOR EMPIRICAL
DESIGN OF EARTHEN WALL STRUCTURES
|
STRENGTH OF UNIT, GROSS AREA |
ALLOWABLE STRESSES CROSS-SECTIONAL AREA |
NOTE 1 |
|
|
Compression |
300 psi |
Normal loading Concentrated loading |
30 psi 45 psi |
|
Modulus of rupture |
55 psi |
Allowable tension without tensile reinforcing |
0 psi |
|
Shear |
N/A |
With special inspection Without special inspection |
8 psi 4 psi |
|
Modulus of elasticity |
60,000 psi |
Allowable deflection |
Less than 1/2% |
Notes:
1. Gross
cross-sectional area shall be calculated on the actual rather than the nominal
dimensions.
R614.7. Lateral support. Earthen walls shall be
laterally supported in the vertical direction and at intersection with other
earthen walls. Support at the top of the
wall shall be in accordance with one of the methods in R614.7.1 or R614.7.2.
R614.7.1. Bond beams. A continuous bond beam system embedded in the
earthen walls, designed to provide lateral support for the walls without the aid
of additional bracing elements such as roof diaphragm. Bond beams of concrete or masonry shall be
not less than the width of the wall, minus six (6) inches (152 mm).
R614.7.1.1. Bond beam anchorage. Bond
beams shall be anchored to earthen walls at intervals of not over forty-eight
(48) inches (1219 mm) by a connection with shear strength of not less than the
shear forces in both directions. The shear between a cast in place concrete
bond beam and the earthen wall shall not exceed one-eighth (1/8) the dead load
at the base of the bond beam unless alternate attachment is provided compatible
with the allowable stresses in Table R614.6.A or International Building Code Table 2109.8.3.1.
R614.7.2. Roof diaphragm. A roof diaphragm complying with other provisions of this code adequate to
provide lateral support may be used to brace earthen walls.
R614.7.2.1. Tie beams. A tie beam is a beam built into the earthen wall for the purpose of
anchoring the roof diaphragm and transferring the lateral perpendicular and
parallel forces. Tie beams shall be
provided for all earthen walls laterally braced by a roof diaphragm.
R614.7.2.2. Tie beam anchorage. Tie beams shall be anchored to earthen walls at intervals of not over
forty-eight (48) inches (1219 mm) by a connection with shear strength of not
less than the shear forces in both directions. The shear between a cast in
place concrete or masonry tie beam and the earthen wall shall not exceed
one-eighth (1/8) the dead load at the base of the bond beam unless alternate
attachment is provided compatible with the allowable stresses in Table R614.6.A
or International
Building Code Table 2109.8.3.1.
R614.8. Lintels.
Earthen walls over openings
shall be supported by steel lintels, reinforced concrete or masonry lintels or
earthen material arches designed to support load imposed. Lintels shall not be supported by rigid
structural columns, frames or posts with rigidities greater than the earthen
wall unless the design allows for the potential for differential
settlements. Small openings less than
twelve (12) inches may be constructed without structural lintels.
R614.9. Shear walls. Earthen walls subject to in-plane loads shall be designed to be tension
free unless tensile reinforcement is provided.
Solid panels less than four (4) feet (1219 mm) shall not be considered
shear walls.
R614.10. Opening jambs. Portions of walls between openings shall be constructed with lengths of
not less than one and one-half (1-1/2) times the thickness of the wall in which
they occur.
R614.11. Freestanding piers. Piers independent of earthen walls shall
be designed to support vertical and horizontal loads unless braced by other
elements of the structure. Tensile
reinforcement shall be provided where tension occurs. When structural posts or columns are provided
within the pier or attachments shall be provided to the earthen wall system to
laterally secure it.
R614.11.1. Pier cap. A solid concrete cap shall be provided at the top of load bearing piers
under all concentrated loads. The cap shall
cover not less than fifty percent (50%) of the top pier.
R614.12. Chases. Chases and recesses in earthen walls shall not be deeper than one-third
(1/3) the thickness of the wall thickness.
The maximum length of a horizontal chase or horizontal projection shall
not exceed four (4) feet (1219 mm), and shall have at least eight (8) inches
(203 mm) of earthen construction in back of the chases and recesses and between
adjacent chases or recesses and at least twelve (12) inches (305 mm) between
the chase and the jambs of openings.
Chases
and recesses in earthen walls shall be designed and constructed so as not to
reduce the required strength or required fire resistance of the wall and in no
case shall a chase or recess be permitted within the required area of a
pier. Earthen walls directly above
chases or recesses wider than sixteen (16) inches (406 mm) shall not be
supported on non-combustible lintels.
R614.13. Stack bond. When the earthen wall is constructed of units, (e.g. adobe brick), units
shall not be laid in stack bond. Units shall, in all locations throughout the
wall system, overlap the courses below by not less than one-third (1/3) the
dimension of the units.
EXCEPTION: Ornamental non-structural elements may be
laid in stack bond if properly tied to the main structure.
R614.14. Metal reinforcement. All
walls shall be anchored at their intersections, at vertical intervals of not
more than sixteen (16) inches (406 mm) with joint reinforcement of at least
nine (9) gage when using earthen units, (e.g. adobe block). Horizontal reinforcement shall be used
throughout the wall system and be continuous at the intersections. Reinforcement used throughout the wall system
shall be not more than four (4) inches narrower than the wall thickness.
R614.15. Veneer. All veneers using earthen materials shall be installed in accordance with
this section. Such veneers shall be
installed with a non-combustible foundation, over concrete masonry, a backing
of wood or cold-formed steel and the veneer shall be not less than four (4)
inches (101 mm) or greater than eight (8) inches (203 mm) in thickness.
R614.15.1.
R614.15.2. Air space. The veneer shall be separated from the sheathing by an air space of a
minimum of one inch (25 mm) but not more than two (2) inches (51 mm). A weather-resistant membrane of fifteen (15)
pound asphalt-saturated felt shall be provided except when veneer is applied over
concrete masonry or concrete backing.
R614.15.3. Flashing. Approved corrosion-resistive flashing shall be provided in the exterior
wall envelope in such a manner as to prevent entry of water into the wall
cavity or penetration of water into the building structural framing
components. The flashing shall extend to
the surface of the exterior wall finish and shall be installed to prevent water
from reentering the exterior wall envelope.
Flashing shall be located beneath the first course of veneer, and at
other points of support, including structural floors, shelf angles and lintels. Approved corrosion-resisting flashing shall
be installed at all of the following locations:
1. At top of all exterior window and door
openings in such a manner as to be leak proof.
2. At
the intersection of chimneys or other masonry construction with frame or stucco
walls, with projection lips on both sides under stucco copings.
3. Under
and at the ends of masonry, wood or metal copings and sills.
4. Where
exterior porches, decks or stairs attach to a wall or floor assembly of
wood-frame construction.
5. At
wall and roof intersections.
R614.15.4. Weep holes. Weep holes shall be provided in the outside withe of masonry walls at a
maximum spacing of thirty-three (33) inches (838 mm) on center. Weep holes shall not be less than
three-sixteenths (3/16) inches (4.8 mm) in diameter. Weep holes shall be located immediately above
the flashing.
R614.16. Buttresses. Earthen walls used as buttresses shall not extend beyond an average
length perpendicular to the wall to be braced a distance of six (6) feet (1830
mm) without consideration to out-of-plane bending of the buttress.
R614.17. Gable end walls. Gable end walls shall be constructed using veneer construction as
required by R614.15 or shall be provided with lateral bracing to prevent
overturn.
R614.18. Ledgers. Ledgers shall not be used to support vertical live and dead loads in
excess of seventy-five (75) pounds per lineal foot unless the tension in the
wall fur to bending from out-of-plane loads and the eccentric load from the
ledger is zero.
R614.19. Material standards. The materials used in earthen wall structures shall comply with the
following material standards. For each
of the tests prescribed in these standards, five (5) full size sample units
shall be selected at random from each lot of units of fraction thereof produced. Mass wall systems such as rammed earth shall
provide five (5) tests for each required standard test series.
R614.19.1. Manufacturers of earthen materials. Established manufacturers of earthen materials shall certify compliance
with these standards. Copies of their
periodic testing shall be supplied to the manufacturer to designers and users
of earthen materials shall include the actual dimensions of units, not nominal
dimensions.
R614.19.2. Onsite earthen materials. Earthen units, mortar, rammed earth wall materials mined, mixed,
formulated, and/or molded on site shall be tested for compliance with these
standards. For individual structures, a
set of tests shall be provided for the first two thousand five hundred (2,500)
square feet of wall and an additional test for each additional two thousand
five hundred (2,500) square feet or portion thereof in the structure. At least one set of tests shall be made for
each structure and for each two thousand five hundred (2,500) square feet of
patio wall. The fabricator of the materials used in the project shall certify
in writing to the building official compliance with these standards. The certification shall include the number of
units site molded, size of the units, volume of material used as mortar, dates
of fabrication, and results of testing of the material. If materials from established manufacturers
and onsite materials are used in the project, copies of records including
sources, quantities, and location of use within the structure shall be provided
to the building official upon request.
R614.19.3. Categories of earthen materials. Type I, II, III, and IV earthen materials are approved for use in
construction of projects designed in accordance with R614.
EXCEPTION:
Type I adobe shall only
be used for repairs and small additions in which new walls do not exceed ten
percent (10%) of the surface area of existing walls of Type I construction and
for structures constructed of a similar material system and for projects
requiring this class of materials to meet historic guidelines.
R614.19.3.1. Required plaster veneer. Adobe of Type I and II shall be protected on the exterior with exterior
plaster meeting the requirements of IBC Section 2512 applied over wire
lath. Type I and II adobe shall not be
used within four (4) inches (102 mm) of the floor or at the top of parapet
walls or near potential sources of water which may effect the stability of the
earth wall system. Other types of adobe
may be left unplastered and may be used without separation from the floor.
R614.19.3.2. Adobe units and mortar. Moisture resistant stabilized adobe units and mortar shall meet the
following testing standards as indicated in Table R614.19.3.2. Type
TABLE R614.19.3.2
|
Material Type |
Dry Compression R614.19.3 |
Wet Compression R614.19.4 |
Modulus of Rupture R614.19.5 |
Absorption <2.5% R614.19.6 |
Absorption <5.0% R614.19.7 |
Moisture Content R614.19.8.1 |
|
I |
X |
|
X |
|
|
X |
|
II |
X |
|
X |
|
X |
X |
|
III |
X |
|
X |
X |
|
X |
|
IV |
|
X |
X |
|
|
X |
“X” indicates that material must pass the test standards
prescribed in this section.
R614.19.3.3. Dry compression strength. Determine
the compressive strength of the required number of samples as required by
R614.19 in accordance with the following procedures.
R614.19.3.3.1. Dry the specimen. Dry
the specimen at a temperature of eighty-five degrees (85° F) +- fifteen degrees
(15° F) (twenty-nine degrees (29° C) +-
nine degrees (9° C)) in an atmosphere having relative humidity of not more than
fifty percent (50%). Weigh the specimen
at one-day intervals until constant weight is attained.
R614.19.3.3.2. Cap the specimen. The
specimen may be suitably capped with calcined gypsum mortar or the bearing
surfaces may be rubbed smooth and true.
Then calcined gypsum is used for capping, conduct the test after the
capping has set and the specimen has been dried to constant weight in
accordance with Item 1 of this section.
R614.19.3.3.3. Test the specimen. Test the specimens in
the position in which the earthen unit is designed to be used. And bed on and cap with a felt pad not less
then one-eighth (1/8) inch (3.2 mm) or more than one-fourth (1/4) inch (6.4 mm)
in thickness.
R614.19.3.3.4. Testing equipment. The
loading head shall completely cover the bearing area of the specimen and the
applied load shall be transmitted through a spherical bearing block of proper
design. The speed of the moving head of
the testing machine shall not be more than 0.05 inches (1.27 mm) per minute.
R614.19.3.3.5. Reporting results. Calculate
the average compressive strength of the specimens tested and report this as the
compressive strength of the block. Units
shall have an average dry compressive strength of three hundred (300) psi (2068
kPa) and no individual unit may have a strength of less than two hundred fifty
(250) psi (1724 kPa).
R614.19.4. Wet compression strength. Determine
the compressive strength of the required number of specimen as required by R614.19 in accordance with the following procedures:
R614.19.4.1. Cap the specimen. The
specimens may be suitably capped with a capping material compatible with water
saturation or the bearing surfaces may be rubbed smooth and true.
R614.19.4.2. Wetting the specimen. Submerge
the specimen under water for not less than eight (8) hours or longer as
required until fully saturated.
R614.19.4.3. Test the specimen. Immediately
test the specimen in the position in which the earthen unit is designed to be
used. Bed on and cap with a felt pad not
less than one-eighth (1/8) inch (3.2 mm) or more than one-fourth (1/4) inch
(6.4 mm) in thickness.
R614.19.4..4. Testing equipment. The
loading head shall completely cover the bearing area of the specimen and the
applied load shall be transmitted through a spherical bearing block of proper
design. The speed of the moving head of
the testing machine shall not be more than 0.05 inch (1.27 mm) per minute.
R614.19.4.5. Reporting results. Calculate
the average compressive strength of the specimens tested and report this as the
compressive strength of the block. Adobe
units shall have an average wet compressive strength of three hundred (300) psi
(2068 kPa). Five (5) samples shall be
tested and no individual unit may have a wet compressive strength of less than
two hundred fifty (250) psi (1724 kPa).
R614.19.5. Modulus of rupture. Adobe
units shall have an average modulus of rupture of fifty (50) psi (345 kPa) when
tested in accordance with the following procedures. Five (5) samples shall be tested and no
individual unit shall have a modulus of rupture of less than thirty-five (35)
psi (241 kPa).
R614.19.5.1. Support conditions. A
cured unit shall be simply supported by two (2) inch diameter (51 mm)
cylindrical supports located two (2) inches (51 mm) in from each end and
extending the full width of the unit.
R614.19.5.2. Loading conditions. A
two (2) inch diameter (51 mm) cylinder shall be placed at midspan parallel to
the supports.
R614.19.5.3. Testing procedure. A
vertical load shall be applied to the cylinder at the rate of five hundred
(500) pounds per minute (37 N/s) until failure occurs.
R614.19.5.4. Modulus of rupture determination. The
modulus of rupture shall be determined by the formula:
Equation R614.19.5.4.1
Fr
= 3WLs/2bt2
Where,
for the purpose of this section only:
B =
Width of the test specimen measured parallel to the loading cylinder, inches
(mm)
Fr
= Modulus of rupture, psi (Mpa)
Ls
= Distance between supports, inches (mm)
T =
Thickness of the test specimen measured parallel to the distance of load,
inches (mm)
W =
The applied load at failure, pounds (N).
R614.19.6. Absorption less than 2.5%. A
four (4) inch (102 mm) cube, cut from an adobe unit fired to a constant weight
in a ventilated oven at two hundred twelve degrees (212° F) to two hundred
thirty-nine degrees (239° F), shall not absorb more than two and one-half
percent (2‑1/2%) moisture by weight when placed upon a constantly
water-saturated, porous surface for seven (7) days. A minimum of five (5) specimens shall be
tested and each specimen shall be cut from a separate unit.
R614.19.7. Absorption less than 5.0%. A
four (4) inch (102 mm) cube, cut from an adobe unit fired to a constant weight
in a ventilated oven at two hundred twelve degrees (212° F) to two hundred
thirty-nine degrees (239° F), shall not absorb more than two and one-half
percent (2‑1/2%) moisture by weight when placed upon a constantly
water-saturated, porous surface for seven (7) days. A minimum of five (5) specimens shall be
tested and each specimen shall be cut from a separate unit.
R614.19.8. Additional requirements. All earthen units shall meet the following requirements:
R614.19.8.1. Moisture content requirements. Earthen
units shall have a moisture content not exceeding four percent (4%) by weight
at the time of use.
R614.19.8.2. Shrinkage cracks. All
earthen units shall not contain more than three (3) shrinkage cracks and any
single shrinkage crack shall not exceed three (3) inches (76 mm) in length or
one-eighth (1/8) inch (3.2 mm) in width.
R614.19.8.3. Soil requirements. Soil
used for moisture resisting adobe units and mortar shall be chemically
compatible with the stabilizing material.
The soil shall contain sufficient clay to bind the particles together
without the aid of stabilizers. The soil
shall contain not more than 0.2 percent of water-soluble salts.
R614.19.9. Cement stabilized rammed earth. Cement
stabilized rammed earth shall meet the following standards. The installer of the wall system shall comply
with the requirements of R614.19.2 for frequency of testing.
R614.19.9.1. Testing before construction. The
installer of cement stabilized rammed earth shall provide the following testing
before issuance of a building permit.
R614.19.9.2. Materials from a licensed sand and gravel
producer. A copy of Proctor ASTM D 698 shall be provided
for each soil type and source or combination of sources. Periodic testing as provided by the supplier
may be supplied to meet this requirement.
The soil shall contain not more than 0.2 percent of water-soluble salts.
R614.19.9.3. Material mined and mixed on site. A
copy of ASTM D 698, ASTM C 117, ASTM C 136, and ASTM D 4318 shall be provided
for each soil type and source or combination of sources. Such testing shall be repeated as required to
assure that all materials to be used have been tested and are represented by
the tests. The soil shall contain not
more than 0.2 percent of water-soluble salts.
R614.19.9.4. Testing required during construction. The
installer of cement stabilized rammed earth shall provide the following tests
made during the construction process. A
certified testing laboratory shall provide field density tests for comparison
to the preconstruction Proctor ASTM D 698, percent moisture ASTM D 2216, dry
density ASTM D 698, and percent moisture ASTM D 1556.
Cement
stabilized rammed earth walls shall meet or exceed ninety-five percent (95%)
maximum dry density (ASTM D 698).
Samples taken from the wall shall exceed three hundred (300) psi
compression (ASTM D 1633) fourteen (14) days after placement.
(Ord. No.
2008.72, 12-11-08)
Sec. R702.
Interior covering.
Table R702.3.5. is hereby amended as follows:
TABLE R702.3.5
MINIMUM THICKNESS AND APPLICATION OF GYPSUM BOARD
|
THICKNESS OF GYPSUM BOARD (inches) |
APPLICATION |
ORIENTATION OF GYPSUM BOARD TO FRAMING |
MAXIMUM SPACING OF FRAMING
MEMBERS (inches o.c.) |
MAXIMUM SPACING OF FASTENERS (inches) |
SIZE OF NAILS FOR APPLICATION TO WOOD FRAMINGc |
|
|
Nailsa |
Screwsb |
|||||
|
1/2 |
Ceiling |
Either
direction |
16 |
7 |
12 |
13 gage, 1-3/8 long, 19/64 head; 0.098 diameter, 1-1/4 long,
annular-ringed; 5d cooler nail, 0.086 diameter, 1-5/8 long,
15/64 head; or gypsum board nail, 0.086 diameter,
1-5/8 long, 9/32 head. |
|
Ceilingd |
Perpendicular |
24 |
7 |
12 |
||
|
Wall |
Either
direction |
24 |
8 |
12 |
||
|
Wall |
Either
direction |
16 |
8 |
16 |
||
|
5/8 |
Ceiling |
Either
direction |
16 |
7 |
12 |
13 gage, 1-5/8 long, 19/64 head; 0.098 diameter, 1-3/8 long,
annular-ringed; 6d cooler nail, 0.092 diameter, 1-7/8 long, 1/4 head; or gypsum
board nail
0.0915 diameter, 1-7/8 long, 19/64 head. |
|
Ceilinge |
Perpendicular |
24 |
7 |
12 |
||
|
Wall |
Either
direction |
24 |
8 |
12 |
||
|
Wall |
Either
direction |
16 |
8 |
16 |
||
|
Application with adhesive |
||||||
|
1/2 or 5/8 |
Ceiling |
Perpendicular |
16 |
16 |
16 |
Same as above for 1/2 and 5/8 gypsum board,
respectively |
|
Ceilingd |
Either direction |
24 |
12 |
16 |
||
|
Wall |
Either direction |
24 |
16 |
24 |
||
For SI: 1 inch =
25.4 mm.
a.
For application without adhesive, a pair of nails spaced not less than 2
inches apart or more than 2-1/2 inches apart may be used with the pair of nails
spaced 12 inches on center.
b.
Screws shall be Type S or W per ASTM C 1002 and shall be sufficiently
long to penetrate wood framing not less than 5/8 inch and metal framing not
less than 3/8 inch.
c.
Where metal framing is used with a clinching design to receive nails by
two edges of metal, the nails shall be not less than 5/8 inch longer than the
gypsum board thickness and shall have ringed shanks. Where the metal framing has a nailing groove
formed to receive the nails, the nails shall have barbed shanks or be 5d,
13-1/2 gage, 1-5/8 inches long, 1-5/64 inch head for ½ inch gypsum board; and
6d, 13 gage, 1-7/8 inches long, 15/64 inch head for 5/8 inch gypsum board.
d.
On ceiling applications to receive a water-based texture material, either
hand or spray applied, the gypsum board shall be applied perpendicular to
framing. When applying a water-based texture material, the minimum gypsum board
thickness shall be 1/2-inch for 16-inch on center framing and 5/8 inch for 24
inch on center framing or 1/2-inch sag-resistant gypsum ceiling board shall be
used.
e.
Type X gypsum board for garage ceilings beneath habitable rooms shall be
installed perpendicular to the ceiling framing and shall be fastened at maximum
6 inches o.c. by minimum 1-7/8 inches 6d coated nails or equivalent drywall
screws.
(Ord. No. 2008.72, 12-11-08)
Sec.
R903. Weather protection.
Section
R903.4.1 is hereby amended as follows:
R903.4.1.
Overflow drains and scuppers. Where roof drains are required, overflow
drains having the same size as the roof drains shall be installed with the
inlet flow line located two (2) inches (51 mm) above the low point of the roof,
or overflow scuppers having three (3) times the size of the roof drains and
having a minimum opening height of four (4) inches (102 mm) shall be installed
in the adjacent parapet walls with the inlet flow located two (2) inches (51
mm) above the low point of the roof served. The installation and sizing of
overflow drains, leaders and conductors shall comply with the International
Plumbing Code.
(Ord. No.
2008.72, 12-11-08)
Sec.
R1007. Clean burning fireplaces.
Section
R1007 is hereby added as follows:
R1007.1. Clean burning fireplaces. The
purpose of this standard is to regulate fireplaces, woodstoves, or other
solid-fuel burning devices to reduce the amount of air pollution caused by
particulate matter and carbon monoxide.
The effective date of the regulations and prohibitions set
forth in this standard took effect on December 31, 1998.
Definitions: For
purposes of this standard, the following words and terms shall be defined as
follows:
FIREPLACE means a built in place masonry hearth and fire
chamber or a factory-built appliance, designed to burn solid fuel or to
accommodate gas or electric log insert or similar device, and which is intended
for occasional recreational or aesthetic use, not for cooking, heating, or
industrial processes.
SOLID FUEL includes but is not limited to wood, coal, or
other nongaseous or non-liquid fuels, including those fuels defined by the
Maricopa County Air Pollution Control Officer as inappropriate fuel to burn in
residential wood-burning devices.
WOODSTOVE means a solid-fuel burning heating appliance
including a pellet stove, which is either freestanding or designed to be
inserted into a fireplace.
R1007.2. Installation restrictions. On
or after the effective date, no person, firm or corporation shall construct or
install a fireplace or a woodstove, and the building official shall not approve
or issue a permit to construct or install a fireplace or a woodstove, unless
the fireplace or woodstove complied with one of the following:
1. A fireplace which has a permanently
installed gas or electric log insert.
2. A fireplace,
woodstove, or other solid-fuel burning appliance which has been certified by
the United States Environmental Protection Agency as conforming to 40 Code of
Federal Regulations Part 60, Subpart AAA as in effect on
3. A fireplace,
woodstove or other solid-fuel burning appliance which has been tested and
listed by a nationally recognized testing agency to meet performance standards
equivalent to those adopted by 40 Code of Federal Regulations Part 60, Subpart
AAA as in effect on
4. A fireplace,
woodstove or other solid-fuel burning appliance which has been determined by
the Maricopa County Air Pollution Control Officer to meet performance standards
equivalent to those adopted by 40 Code of Federal Regulations Part 60, Subpart
AAA as in effect on
5. A fireplace
which has a permanently installed woodstove insert which complies with
subparagraphs 2, 3, or 4 above.
R1007.3. The following
installations are not regulated by this standard and are not prohibited by this
standard:
1. Furnace,
boilers, incinerators, kilns, and other similar space heating or industrial
process equipment.
2. Cook-stoves,
barbecue grills, and similar appliances designed primarily for cooking.
3. Fire pits,
barbecue grills, and other outdoor fireplaces.
R1007.4.
Fireplace or woodstove alterations prohibited.
R1007.4.1. On or after the effective date, no person,
firm or corporation shall alter or remove a gas or electric log insert or a
woodstove insert from a fireplace for purposes of converting the fireplace to
directly burn wood or other solid fuel.
R1007.4.2. On or after the effective date, no person,
firm or corporation shall alter a fireplace, woodstove or other solid fuel
burning appliance in any manner that would void its certification or
operational compliance with the provisions of this standard.
R1007.5.
Permits required. In
addition to the provisions and restrictions of this standard, construction,
installation or alteration of all fireplaces, woodstoves and other gas,
electric or solid-fuel burning appliances and equipment shall be done in
compliance with provisions of this code and shall be subject to the permits and
inspections.
(Ord. No.
2008.72, 12-11-08)
Sec. M1307.
Appliance installation.
Section M1307.3 is hereby amended as follows:
M1307.3. Elevation of ignition
source. Appliances
having an ignition source shall be elevated such that the source of ignition is
not less than eighteen (18) inches (457 mm) above the floor in garages. For the purpose of this section, rooms or
spaces that are not part of the living space of a dwelling unit and that
communicate with a private garage through openings shall be considered to be
part of the private garage.
EXCEPTIONS:
1. Elevation of the ignition source is not
required for appliances that are listed as flammable vapor resistant and for
installation without elevation.
2. Direct-vent
appliances that obtain all combustion air directly from the outdoors.
3. Clothes
dryers installed in private garages.
Section M1307.6 is hereby added as follows:
M1307.6. Liquefied petroleum
appliances. LPG appliances shall
not be installed in an attic, pit or other location that would cause a ponding
or retention of gas.
(Ord. No.
2008.72, 12-11-08)
Sec. M1411. Heating and cooling equipment.
Section M1411.3.2 is hereby amended as follows:
M1411.3.2. Drain pipe materials and sizes. Components of the condensate disposal system
shall be cast iron, galvanized steel, copper, polybutylene, polyethylene, ABS,
CPVC or PVC pipe or tubing. All
components shall be selected for the pressure and temperature rating of the
installation. Condensate waste and drain
line size shall not be less than three-fourths (3/4) inch (91 mm) internal
diameter and shall not decrease in size from the drain pan connection to the
place of condensate disposal. Where the
drain pipes from more than one unit are manifolded together for condensate
drainage, the pipe or tubing shall be sized in accordance with an approved
method. All horizontal sections shall be
installed with a uniform alignment at a uniform slope in the direction of
discharge of not less than one-eighth (1/8) unit vertical in twelve (12) units’
horizontal (one-percent slope).
(Ord. No.
2008.72, 12-11-08)
Sec. M1701. General.
Section M1701.4 is hereby amended as follows:
M1701.4.
Prohibited sources.
Combustion air ducts and openings shall not connect appliance
enclosures with space in which the operation of a fan may adversely affect the
flow of combustion air. Combustion air
shall not be obtained from an area in which flammable vapors present a
hazard. Fuel-fired appliances shall not
obtain combustion air from any of the following rooms or spaces:
1. Sleeping rooms.
2. Bathrooms.
3. Toilet rooms.
EXCEPTION: The following
appliances may be located in sleeping rooms, bathrooms and toilet rooms:
1. Appliances
installed in an enclosure in which all combustion air is taken from the
outdoors and the enclosure is equipped with a solid weather-stripped door and self-closing
device.
2. Direct-vent
appliances that obtain all combustion air directly from the outdoors.
(Ord. No.
2008.72, 12-11-08)
Sec. M1703. All
air from outdoors.
Section M1703.2 is hereby amended as follows:
M1703.2. Two openings or ducts. Outside combustion air shall be supplied through
openings or ducts, as illustrated in Figures M1703.2(1), M1703.2(2), M1703.2(3)
and M1703.2(4). One opening shall be
within twelve (12) inches (305 mm) of the top of the enclosure, and one within
twelve (12) inches (305 mm) of the top of the enclosure, and one within twelve
(12) inches (305 mm) of the bottom of the enclosure. For LPG appliances, any duct serving the
lower opening shall be at the floor level and slope to the outdoors without
traps or pockets. Openings are permitted
to connect to spaces directly communicating with the outdoors, such as
ventilated crawl spaces or ventilated attic spaces. The same duct or opening shall not serve both
combustion air openings. The duct
serving the upper opening shall be level or extend upward from the appliance.
(Ord. No.
2008.72, 12-11-08)
Sec. G2406.
Appliance location.
Section G2406.2 (303.3) is hereby amended as follows:
G2406.2 (303.3). Prohibited locations. Appliances shall not be located in sleeping
rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a
space that opens only into such rooms or spaces, except where the installation
complies with one of the following:
1. The appliance
is a direct-vent appliance installed in accordance with the conditions of the
listing and the manufacturer’s instructions.
2. Vented rooms
heaters, wall furnaces, vented decorative appliances, vented gas fireplaces,
vented gas fireplace heaters and decorative appliances for installation in vented
solid fuel-burning fireplaces are installed in rooms that meet the required
volume criteria of Section G2407.5.
3. A single
wall-mounted unvented room heater is installed in a bathroom and such unvented
room heater is equipped as specified in Section G2445.6 and has an input rating
not greater than six thousand (6,000) Btu/h (1.76 kW). The bathroom shall meet the required volume
criteria of Section G2407.5.
4. A single
wall-mounted unvented room heater is installed in a bedroom and such unvented room
heater is equipped as specified in Section G24445.6 and has an input rating not
greater than ten thousand (10,000) Btu/h (2.93 kW). The bedroom shall meet the required volume
criteria of Section G2407.5.
5. Liquefied
Petroleum (LPG) appliances shall not be installed in an attic, pit or other
location that would cause ponding or retention of gas.
(Ord. No.
2008.72, 12-11-08)
Sec. G2408.
Installation.
Section G2408.2 (305.3) is hereby amended as follows:
G2408.2 (305.3). Elevation of ignition source. Equipment and appliances having an ignition
source shall be elevated such that the source of ignition is not less than
eighteen (18) inches (457 mm) above the floor in hazardous locations and public
garages, private garages, repair garages, motor fuel-dispensing facilities and
parking garages. For the purpose of this
section, rooms or spaces that are not part of the living space of a dwelling
unit and that communicate directly with a private garage through openings shall
be considered to be part of the private garage.
EXCEPTIONS:
1. Elevation of the ignition source is not
required for appliances that are listed as flammable vapor resistant and for
installation without elevation.
2. Direct-vent
appliances that obtain all combustion air directly from the outdoors.
3. Clothes
dryers installed in private garages.
(Ord. No.
2008.72, 12-11-08)
Sec. G2415.
Piping system installation.
Section G2415.9 (404.9) is hereby amended as follows:
G2415.9
(404.9). Minimum burial depth. Underground
piping systems shall be installed a minimum depth of twelve (12) inches (305
mm) below grade, for metal, and eighteen (18) inches for plastic piping.
(Ord. No.
2008.72, 12-11-08)
Sec. G2417.
Inspection, testing and purging.
Section G2417.4 (406.4) is hereby amended as follows:
G2417.4 (406.4). Test
pressure measurement. Test pressure
shall be measured with a manometer or with a pressure-measuring device designed
and calibrated to read, record, or indicate a pressure loss caused by leakage
during the pressure test period. The
source of pressure shall be isolated before the pressure tests are made.
G2417.4.1
(406.4.1). Test pressure. The test pressure to be used shall be no less
than ten (10) pounds per square inch (69 kPa) gauge pressure, or where approved
by the building official, the piping and valves may be tested at a pressure of
at least six (6) inches (152.4 mm) of mercury, measured with a manometer or
slope gauge. For welded piping, and for
piping carrying gas at pressures in excess of fourteen (14) inches (0.4 m)
water column pressure, the test pressure shall be no less than sixty (60)
pounds per square inch (413 kPa). Where
the test pressure exceeds one hundred twenty-five (125) psig (862 kPa gauge),
the test pressure shall not exceed a value that produces a hoop stress in the
piping greater than fifty percent (50%) of the specified minimum yield strength
of the pipe.
G2417.4.2
(406.4.2). Test duration. Test duration shall be not less fifteen (15)
minutes or for welded pipe and piping carrying gas at pressures in excess of
fourteen (14) inches (0.4 m) water column pressure, the test duration shall be
not less than thirty (30) minutes. The
duration of the test shall not be required to exceed twenty-four (24) hours.
Section G2417.4.3 is hereby added as follows:
G2417.4.3. Test gauges. Tests required by this code which are
performed utilizing dial gauges shall be limited to gauges having the following
pressure increments or graduations.
G2417.4.3.1. Required pressure tests of ten (10) pounds
(69 kPa) or less shall be performed with gauges having increments of one-tenth
(1/10) pound (0.69 kPa) or less.
G2417.4.3.2. Required pressure tests exceeding ten (10)
pounds (69 kPa) but less than one hundred (100) pounds (690 kPa) shall be
performed with gauges having increments of one pound (7 kPa) or less.
G2417.4.3.3. Required pressure tests exceeding one hundred
(100) pounds (690 kPa) shall be performed with gauges having increments two (2)
psi (14 kPa) or less.
G2417.4.3.4. Pressure tests required by this code, which
are performed utilizing dial gauges, shall be limited to a gauge having a
maximum gauge rating not exceeding twice the applied test pressure.
(Ord. No.
2008.72, 12-11-08)
Sec.
P2503. Inspection and tests.
Section
P2503.8 is hereby amended as follows:
P2503.8. Test gauges. Gauges
used for testing shall be as follows:
1. Tests requiring a pressure of ten (10) psi
or less shall utilize a testing gauge having increments of 0.10 psi or less.
2. Tests requiring a pressure of ten (10) psi
but less than or equal to one hundred (100) psi shall utilize a testing gauge
having increments of one psi or less.
3. Tests requiring a pressure of greater than
one hundred (100) psi shall utilize a testing gauge having increments of two
(2) psi or less.
Pressure
tests required by this code, which are performed utilizing dial gauges, shall
be limited to a gauge having a maximum gauge rating not exceeding twice the
applied test pressure.
(Ord. No.
2008.72, 12-11-08)
Sec.
P2603. Structural and piping protection.
Section
P2603.6.1 is hereby amended as follows:
P2603.6.1.
Sewer depth. Building sewers
shall be a minimum of twelve (12) inches (305 mm) below grade.
(Ord. No.
2008.72, 12-11-08)
Sec.
P2801. General.
Section
P2801.5.1 is hereby amended as follows:
P2801.5.1.
Pan size and drain. The pan shall not be less than one and
one-half (1.5) inches (38 mm) deep and shall be of sufficient size and shape to
receive all dripping or condensate from the tank or water heater. The pan shall be drained by an indirect waste
pipe having a minimum diameter of three-fourths (3/4) inch (19 mm) installed
with a uniform alignment at a uniform slope in the direction of discharge of
not less than one-eighth (1/8) unit vertical in twelve (12) units’ horizontal
(one-percent slope).
(Ord. No.
2008.72, 12-11-08)
Sec.
P2803. Relief valves.
Section
P2803.6.1, Item 10 is hereby amended as follows:
P2803.6.1.
Requirements of discharge pipe.
The discharge piping serving a pressure-relief valve, temperative-relief
valve or combination valve shall:
10. Terminate not less than six (6) inches (152
mm) and not more than twenty-four (24) inches (610 mm) above finished grade.
(Ord. No.
2008.72, 12-11-08)
Sec. P3001.
General.
Section P3001.4 is hereby added as follows:
P3001.4. Sewer required. Every building in which plumbing fixtures are
installed and all premises having drainage piping shall be connected to a
public sewer, where available, or an approved private disposal system in
accordance with the Maricopa County Health Department Environmental Service
Division. The public sewer may be
considered as not being available only when so determined by the Maricopa
County Health Department Environmental Service Division.
(Ord. No.
2008.72, 12-11-08)
Sec. E3503.
Service, feeder and grounding electrode conductor sizing.
Table E3503.1 is hereby amended as follows:
TABLE E3503.1
SERVICE CONDUCTORS AND GROUNDING
ELECTRODE CONDUCTOR SIZING
|
Conductor Types and
Sizes for 120/240-Volt and 120/208-Volt, 3-Wire, Single-Phase Dwelling
Services and Feeders. Conductor Types RH, RHH, RHW, RHW-2, THHN, THHW, THW,
THW-2, THWN, THWN-2, XHHW, XHHW-2, SE, USE, USE-2 |
|||||
|
Copper (AWG or kcmil) |
Aluminum or
Copper-Clad Aluminum (AWG or kcmil) |
Service or Feeder Rating (Amperes) |
Min. Grounding
Electrode Conductor sizea (AWG) |
||
|
|
≤ 30°C |
> 30°C |
Copper |
Aluminum |
|
|
4 |
2 |
100 |
---- |
8b |
6c |
|
3 |
1 |
110 |
---- |
8b |
6c |
|
2 |
1/0 |
125 |
100 |
8b |
6c |
|
1 |
2/0 |
150 |
125 |
6c |
4 |
|
1/0 |
3/0 |
175 |
150 |
6c |
4 |
|
2/0 |
4/0 |
200 |
175 |
4d |
2d |
|
3/0 |
250 |
225 |
200 |
4d |
2d |
|
4/0 |
300 |
250 |
225 |
2d |
1/0d |
|
250 |
350 |
300 |
250 |
2d |
1/0d |
|
350 |
500 |
350 |
300 |
2d |
1/0d |
|
400 |
600 |
400 |
350 |
1/0d |
3/0d |
a. Where protected by a metal raceway,
grounding electrode conductors shall be electrically bonded to the metal
raceway at both ends.
b. No. 8 grounding electrode conductors shall be protected with
metal conduit or nonmetallic conduit.
c. Where not protected, No. 6 grounding
electrode conductors shall closely follow a structural surface for physical
protection. The supports shall be spaced not more than 24 inches on center and
shall be within 12 inches of any enclosure or termination.
d. Where the sole grounding electrode system
is a ground rod or pipe as covered in Section E3508.2, the grounding electrode
conductor shall not be required to be larger than No. 6 copper or No. 4
aluminum. Where the sole grounding electrode system is the footing steel as
covered in Section E3508.1.2, the grounding electrode conductor shall not be
required to be larger than No. 4 copper conductor.
CAUTION - UTILITY COMPANY CONDUCTOR SIZE REQUIREMENTS MAY VARY. CONSULT WITH SERVING UTILITY PRIOR TO INSTALLATION.
(Ord. No.
2008.72, 12-11-08)
Sec. E3601.
General.
Section E3601.1 is hereby amended as follows:
E3601.1. Scope.
This
chapter covers branch circuits and feeders and specifies the minimum required
branch circuits, the allowable loads and the required overcurrent protection
for branch circuits and feeders that serve less than one hundred percent (100%)
of the dwelling unit load. Feeder
circuits that serve one hundred percent (100%) of the dwelling load shall be
sized in accordance with the procedures in Chapter 35. Aluminum conductors smaller than #8 shall not
be used for lighting or power circuits indoors.
(Ord. No.
2008.72, 12-11-08)
Sec. E3802.
Ground-fault and arc-fault circuit-interrupter protection.
Section E3802.11 is hereby amended as follows:
E3802.11. Bedroom
receptacles. All one hundred twenty-five
(125) volt, single-phase, fifteen (15) or twenty (20) ampere receptacles installed in dwelling unit bedrooms
shall be protected by an arc-fault circuit interrupter listed to provide
protection of the entire branch circuit that supplies such receptacles.
Section E3802.12 is hereby amended as follows:
E3802.12. Arc-fault circuit interrupter protection.
E3802.12.1. Definition: Arc-fault circuit interrupter
(AFCI). A device intended to provide
protection from the effects of arc faults by recognizing characteristics unique
to arcing and by functioning to de-energize the circuit when an arc fault is
detected.
E3802.12.2. Dwelling units. All one hundred twenty (120) volt, single
phase, fifteen (15) and twenty (20) ampere branch circuits supplying outlets
installed in dwelling unit family rooms, dining rooms, living rooms, parlors,
libraries, den, bedrooms, sunrooms, recreation rooms, closets, hallways, or
similar rooms or areas shall be protected by a listed arc-fault circuit
interrupter, combination-type, install to provide protection of the branch
circuit.
FPN No. 1: For information on types of arc-fault circuit
interrupters, see UL 1699-1999, Standard for Arc-Fault Circuit Interrupters.
FPN No. 2: See 11.6.3(5) of NFPA 72-2007, National Fire
Alarm Code, for information related to secondary power supply requirements for
smoke alarms install in dwelling units.
FPN No. 3: See 2008 National Electrical Code, Article 760.41(B)
and 760.121(B) for power supply requirements for fire alarm systems.
EXCEPTIONS:
1. Where RMC, IMC,
EMT or steel armorded cable, Type AC, meeting the requirements of 2008 National
Electrical Code, Article 250.118 using metal outlet and junction boxes installed
for the portion of the branch circuit between the branch-circuit overcurrent
device and the first outlet, it shall be permitted to install a combination
AFCI at the first outlet to provide protection for the remaining portion of the
branch circuit.
2. Where a branch
circuit to a fire alarm system installed in accordance with 2008 National
Electrical Code, Article 760.41(B) and 760.121(B) in installed in RMC, IMC, EMT
or steel armored cable, Type AC, meeting the requirements of 2008 National
Electrical Code, Article 250.118, with outlet and junction boxes, AFCI
protection shall be permitted to be omitted.
(Ord. No.
2008.72, 12-11-08)
Sec. E3808.
Grounding.
Section E3808.8 is hereby amended as follows:
E3808.8. Types of
equipment grounding conductors. The equipment grounding conductor run with
or enclosing the circuit conductors shall be one or more or a combination of
the following:
1. A copper or
other corrosion-resistant conductor. This conductor shall be solid or stranded;
insulated, covered, or bare; and in the form of a wire or a busbar of any
shape.
2. Threaded rigid
metal conduit and fittings.
3. Threaded
intermediate metal conduit and fittings.
4. Electrical
metallic tubing with an individual equipment grounding conductor.
5. Flexible metal
conduit with an individual equipment grounding conductor or where both the
conduit and fittings are listed for grounding.
6. Armor of Type
AC cable with an individual equipment grounding conductor.
7. Surface metal
raceway.
8. Metal-clad
cable with an individual equipment grounding conductor or, where both the cable
and fittings are listed for grounding.
9. Liquid-tight
flexible metal conduit with an individual equipment grounding conductor or
where both the conduit and fittings are listed for grounding.
(Ord. No.
2008.72, 12-11-08)
Sec. E4101.
Swimming pools.
Section E4101.1 is hereby amended as
follows:
E4101.1. Scope. The provisions of Article 680 of the 2008
National Electrical Code shall apply to the construction and installation of
electrical wiring and equipment associated with all swimming pools, wading
pools, decorative pools, fountains, hot tubs, and spas, and hydromassage
bathtubs, whether permanently installed or storable, and shall apply to
metallic auxiliary equipment, such as pumps, filters, and similar equipment.
(Ord. No.
2008.72, 12-11-08)
Appendix G.
Swimming pools, spas, and hot tubs.
Section AG102 is hereby amended as follows:
SWIMMING POOL. Any
structure intended for swimming or recreational bathing that contains water
over eighteen (18) inches (430 mm) deep.
This includes in-ground, above-ground, and on-ground swimming pools, hot
tubs, and spas.
Section AG105.2, Outdoor
swimming pool, Item 1 is hereby amended as follows:
1. The top of the barrier
shall be at least five (5) feet (1525 mm) above grade measured on the side of
the barrier that faces away from the swimming pool. The maximum vertical clearance between grade
and the bottom of the barrier shall be two (2) inches (51 mm) measured on the
side of the barrier that faces away from the swimming pool. Where the top of
the pool structure is above grade, such as an aboveground pool, the barrier may
be at ground level, such as the pool structure, or mounted on the top of the
pool structure. Where the barrier is
mounted on top of the pool structure, the maximum vertical clearance between
the top of the pool structure and the bottom of the barrier shall be four (4)
inches (102 mm).
Section AG105.5 is hereby amended as follows:
AG105.5. Barrier exceptions:
1. Spas or hot
tubs with a safety cover which complies with ASTM F 1346, as listed in Section
AG107, shall be exempt from the provisions of this appendix.
2. Where the
premises upon which a swimming pool, spa, or hot tub is located adjoins that
body of water recorded as Tract S of The Lakes, an enclosure parallel to the
bank is not required; provided, that an abutting enclosure, conforming to
AG105, extends horizontally to the lakeside edge of the lake bank or beyond. For purposes of this exception, the word
abutting shall mean terminating at the point of contact with the lakeside edge
of the bank.
Section AG105.6 is hereby added as follows:
AG105.6. Unenclosed pools. It is hereby declared to be a public nuisance
and dangerous to the public health, safety, and welfare to maintain an outdoor
swimming pool, spa or hot tub in the city unless enclosed in accordance with
AG105. It shall be the responsibility of
both the property owner and the occupant of the premises to install and
maintain the fences, locks, latches, alarms, and gates in good condition and
proper working order when water is in the pool, and either or both may be
deemed in violation of this chapter for failure to do so.
Section AG105.7 is added as follows:
AG105.7. Prerequisites to issuance of building permit. A building permit shall not be issued for any
swimming pool, spa or hot tub unless the plans for such pool provide for an
enclosure as required by this article.
Section AG105.8 is added as follows:
AG105.8. Final inspection and approval. No swimming pool, spa or hot tub shall be
filled in whole or in part with water unless the pool enclosure has been
installed in accordance with this article and approved by the development
services manager or authorized representative.
(Ord. No. 2008.72, 12-11-08)
Appendix K. Sound transmission.
Section AK102.1 is amended as follows:
AK102.1 General.
Airborne sound insulation for walls and floor-ceiling assemblies
separating dwelling units from each other shall meet a Sound Transmission Class
(STC) rating of no less than fifty (50) (forty-five (45) if field tested) when
tested in accordance with ASTM E 90. Penetrations or openings in construction
assemblies for piping; electrical devices; recessed cabinets; bathtubs;
soffits; or heating, ventilation or exhaust ducts shall be sealed, lined,
insulated or otherwise treated to maintain the required rating.
Section AK103.1 is amended as follows:
AK103.1. General.
Floor/ceiling assemblies between dwelling units or between a dwelling
unit and a public or service area within a structure shall have an Impact
Insulation Class (IIC) of no less than fifty (50) (forty-five (45) if field
tested) when tested in accordance with ASTM E 492.
(Ord. No. 2008.72, 12-11-08)
Secs. 8-301—8-399.
Reserved.