ARTICLE IX. INTERNATIONAL ENERGY CONSERVATION CODE
Sec. 8-900. Adopted; where filed; amendments.
(a) That certain document known as the
"International Energy Conservation Code, 2006 Edition," which has
been published as a code in book form by the International Code Council,
chapters two through six, three (3) copies with amendments of which are on file
in the office of the city clerk, and this same code and appendices are hereby
referred to, adopted and made a part hereof, as if fully set out in this article.
(b) The provisions of this article, other than
subsections (a) and (b) of this section, are amendments to the International
Energy Conservation Code as now or hereafter adopted in subsection (a). All sections in this article, other than
subsections (a) and (b) of this section, shall be considered to be both a part
of this code and a part of the International Energy Conservation Code.
(Ord.
No. 2008.72, 12-11-08)
Charter
reference—Adoption
by reference, § 2.14.
State law reference—Adoption by
reference, A.R.S. § 9-801 et seq.
Sec. 401. General.
Section
401.2 is hereby amended as follows:
401.2. Compliance. Projects shall comply with Sections 401,
402.4, 402.5, 402.6 and 403 (referred to as the mandatory provisions) and
either:
1. Sections
402.1 through 402.3 (prescriptive); or
2. Section
404 (performance).
As an alternative, additions,
alterations, remodels, and repairs may comply with the department’s standard
energy conservation details.
(Ord.
No. 2008.72, 12-11-08)
Sec. 403.
Systems (Mandatory).
Section
403.2.1 is hereby amended as follows:
403.2.1. Insulation. Supply
and return ducts shall be insulated to a minimum of R-8. Ducts in floor trusses shall be insulated to a
minimum of R-6.
EXCEPTIONS:
1. Ducts or portions thereof located
completely inside the building thermal envelope.
2. Supply and return ducts may be insulated
to a minimum of R-6 when one or more of the following conditions are met:
·
Minimum
seer rating of space heating/cooling system is 14.
·
Maximum
U-factor is 0.64 and maximum SHGC is 0.35 for all fenestration products.
·
Wall
insulation minimum R-value is R-19.
·
Residential
buildings that meet the requirements of Sections 103.1.1 or 404.
(Ord.
No. 2008.72, 12-11-08)
Secs.
8-901—8-999. Reserved.